U-Value Calculator

Sets the standard inside and outside surface resistances.
Standard resistance for a still, unventilated air gap.
Layers, outside face inward
Use the limiting value from the Approved Document that applies to your project.
U-value—

Enter each layer's thickness and thermal conductivity. The calculator sums the resistances and returns the U-value, with the working set out so it can be checked by building control.

How do you calculate a U-value?

A U-value is one divided by the total thermal resistance of the build-up. Add the inside surface resistance, each layer's thickness in metres divided by its thermal conductivity, any unventilated air cavity, and the outside surface resistance, then take the reciprocal. A lower U-value means less heat lost per square metre.

How to use this calculator

  1. Choose the elementWall, roof or floor. This sets the surface resistances, which differ because convection carries heat away differently depending on whether the flow is sideways, upward or downward.
  2. Enter the layers from outside inThickness in millimetres and lambda in watts per metre kelvin. Use the manufacturer's declared lambda rather than a generic table value — the spread within a material class is wide enough to matter.
  3. Add the cavity if one existsAn unventilated air gap of 25 mm or more carries a standard resistance. A ventilated cavity contributes almost nothing and a partially filled one behaves differently again.
  4. Enter the limiting value to check complianceApproved Document L sets limiting U-values by element, and they change between editions. Enter the figure for your project rather than trusting a number quoted in an article.

How the calculation works

Thermal resistances add. Each layer resists heat flow in proportion to its thickness and inversely to its conductivity, so its resistance is thickness in metres divided by lambda. A 100 mm layer of rigid insulation at 0.022 W/m·K contributes 4.55 m²K/W. The same thickness of brick at 0.77 contributes 0.13 — thirty-five times less.

Two more resistances sit at the faces. Rsi accounts for the still air film against the internal finish and Rse for the weather side. BS EN ISO 6946 gives standard values of 0.13 and 0.04 for walls, 0.10 and 0.04 for roofs, and 0.17 and 0.04 for floors.

Add everything and take the reciprocal. That final inversion is why the arithmetic feels unintuitive: doubling the insulation does not halve the U-value, because the masonry, plaster and surface films are still in the total and become proportionally more significant as the insulation improves.

FormulaU = 1 ÷ (Rsi + Σ(d ÷ λ) + Rcav + Rse)

Worked example: a traditional UK cavity wall

Take 102 mm facing brick at λ 0.77, 100 mm of rigid PIR insulation at λ 0.022, 100 mm of lightweight blockwork at λ 0.15, and 13 mm of plasterboard at λ 0.21.

The layer resistances are 0.132, 4.545, 0.667 and 0.062 m²K/W. Adding the wall surface resistances of 0.13 and 0.04 gives a total R of 5.576, so U = 1 ÷ 5.576 = 0.18 W/m²K.

Now swap the lightweight block for a dense concrete one at λ 1.13. That layer drops from 0.667 to 0.088, the total falls to 4.997, and the U-value rises to 0.20. Changing nothing but the inner leaf block has worsened the wall by more than ten per cent — which is why block specification appears on drawings and why substituting on site without checking is a real problem.

Typical lambda values

Treat these as a starting point for testing a build-up. For anything submitted for approval, use the declared lambda from the product's technical data sheet.

MaterialTypical λ (W/m·K)
Phenolic insulation board0.020 – 0.022
PIR / PUR insulation board0.022 – 0.028
Expanded polystyrene (EPS)0.032 – 0.038
Mineral wool quilt0.038 – 0.044
Wood fibre board0.038 – 0.050
Aircrete block0.11 – 0.18
Softwood timber0.13
Plasterboard0.21 – 0.25
Facing brick0.77
Dense concrete block1.13 – 1.75
Sand and cement screed1.15

Where the simplified method falls short

This calculator treats every layer as continuous. Real construction rarely is. Timber studs bridge insulation in a frame wall, joists bridge a ceiling, and mortar joints bridge lightweight blockwork — and every one of those bridges conducts far better than the material around it.

The full BS EN ISO 6946 combined method handles this by calculating an upper and lower resistance limit and averaging them, weighted by the proportion of area each path occupies. For a timber-frame wall at 600 mm centres, roughly 15 per cent of the area is timber, and ignoring it flatters the result by 10 to 20 per cent.

Thermal bridging at junctions is a separate problem again. Corners, reveals, lintels and wall-floor junctions all lose heat at a rate a plane element calculation cannot capture, and they are accounted for through psi values rather than U-values. On a well-insulated modern house, junction losses can approach the total plane-element loss.

None of that makes this calculation useless. It is exactly the right tool for comparing build-ups and testing whether an idea is worth developing. It is not a compliance submission.

Approved Document L applies in England, with separate documents for Wales, Scotland's Section 6 and Northern Ireland's Part F. Limiting U-values differ between them and change between editions, which is why this tool asks you to enter the target rather than storing one.

Assumptions and limitations

  • Layers are treated as homogeneous — no correction for timber studs, joists or mortar bridging
  • Standard surface resistances from BS EN ISO 6946, not adjusted for sheltered or exposed sites
  • Ground floor calculations ignore the perimeter-to-area ratio, which materially affects a real floor U-value
  • Air cavities are assumed unventilated; ventilated and partially filled cavities behave differently
  • No allowance for mechanical fixings penetrating insulation, or air gaps behind poorly fitted boards
  • A design figure only — workmanship on site is the commonest reason a finished element underperforms

Questions people ask about this in United Kingdom

What is a good U-value for a wall?

For new build in the UK, external walls are typically designed at or below 0.18 W/m²K, with better performance common where a fabric-first approach is being taken. Limiting values are set in Approved Document L in England, with separate documents for Wales, Scotland and Northern Ireland, and they change between editions.

Check the figure that applies to your project rather than relying on a number quoted in an article.

Is a higher or lower U-value better?

Lower. A U-value is a rate of heat loss per square metre per degree, so a smaller number means less heat escaping. It runs opposite to most building metrics, which is why the R-value — total thermal resistance, where higher is better — is sometimes quoted instead.

What is the difference between U-value and R-value?

They are reciprocals. R-value is the total thermal resistance of a build-up and higher is better. U-value is one divided by that resistance and lower is better. A wall with an R of 5 has a U of 0.2.

Does this calculator work for timber-frame walls?

Only approximately. Timber studs conduct considerably better than the insulation between them, so a real timber-frame U-value needs the full combined method, averaging an upper and lower resistance limit weighted by area. Treating a studded layer as homogeneous flatters the result, typically by 10 to 20 per cent.

Why is my calculated U-value different from the insulation manufacturer's figure?

Because the manufacturer quotes lambda for the board alone, not a U-value for your wall. The finished element also contains masonry, plaster, cavities and surface films, all of which sit in the total resistance and dilute the insulation's contribution.

Can I use this for a building control submission?

Use it to develop and compare build-ups. A submission normally needs a calculation accounting for bridging by the full combined method, plus junction psi values, and for a dwelling it feeds into a SAP assessment rather than standing alone. This tool tells you whether a build-up is worth pursuing.

The same calculator for other markets

The maths is identical everywhere. These versions use local units, currency and worked examples.

Method, source and review date

How it is worked out
BS EN ISO 6946 combined method, simplified for homogeneous layers
Formula used
U = 1 ÷ (Rsi + Σ(thickness ÷ λ) + Rcavity + Rse)
Last reviewed
Confidence
High

Spotted a figure that has moved, or a formula you can show is wrong? Tell us — send a correction. Fixes to rates and formulas are treated as urgent.

Disclaimer

This is a planning estimate, not a substitute for a design signed off by a qualified engineer. Anything structural, electrical or gas-related must be checked and certified by a competent person before it is built or connected.